The 5000 Series Airestat CO2 是一种壁装式,用来测控二氧化碳浓度
的变送器。双色发光二极管(以红、黄、绿三色)来显示二氧化碳浓
度。输出兼容模拟信号(0-10V) 与数字信号 (RS232/TTL),提供被动
温度输出。
产品特点:
Telaire
Model No CO2 Temp LED GE Logo
T5001 √ √
T5003 √ √ √
T5005 √ √ √
T5007 √ √ √ √
产品详述:
取样方法: 红外线试验法 (NDIR),镀金光学, (with Telaire’s
patented ABC Logic self calibration algorithm).
漫射取样.
测量范围: 0-2,000 ppm 工厂校准. Output scalable using UIP
up to 3,000 ppm with resulting decrease in sensor
accuracy
精确性: +/- 100 ppm @22°C (72°F) when compared with a
factory reference.
温度依存性: 0.2% FS per °C
稳定性: < 2% of FS over life of sensor (15 years typical)
非线性: < 1% of FS
压力依存性: 0.13% of reading per mm Hg
校准间隔: Not required *
响应时间: TBD, pending verification tests.
Estimated at 3-5 minutes for 90% step change.
启动时间: < 2 minutes (operational)
10 minutes (maximum accuracy)
操作条件: 0 to 50°C (32 to 122°F)
0 to 95% RH, non condensing
贮藏条件: -20 to 70°C (-4 to 158°F)
0 to 95% RH, non condensing
温度
NTC 20k Thermistor
输出 Analog: 0-10V (100 Ohms output impedance)
Digital: RS-232 (TTL Level) communication
with Telaire UIP software.
连接: Screw terminals for 18 – 28 AWG.
电源要求: 18 - 30 VAC RMS, 50/60Hz or 18 - 42 VDC,
polarity protected
功率: 1.75 VA average, 3.25 VA peak
AGENCY/CERTIFICATIONS: FCC Part 15 Class B, CE, ROHS, WEEE
保修期: 24 个月
* 注意: 自动校准背景,即ABC Logic™,是一种专利的自
动校准技术。应用范围:在一个14日的周期中浓
度至少有三次下降到外部环境条件(大约400
ppm)-特别是无操作的状态下。经两周的操作可
达到完全精准。
上一页:
SS-668烟雾传感器下一页:
风道二氧化碳变送器