INTL-SENSOR > cases > SCHMIDT Flow Sensors for Cleanroom

SCHMIDT Flow Sensors for Cleanroom


http://www.intl-sensor.com    Time:2010/3/18 11:55:29    Count : 2510 times
SCHMIDT  Flow Sensors for Cleanroom

  SS 20.515/516 SS 20.400 / 23.400 SS 20.415 SS 20.500
Product code SS 20.515 / 516 SS 20.400 / SS 23.400 SS 20.415 SS 20.500
Application Filter monitoring, Room monitoring Flow direction (turbulence degree) Flow direction (turbulence degree) Filter monitoring, Room monitoring if corrosive medias are present
Sensor head Dumb-bell head Thermopile head Thermopile head Dumb-bell head
Measuring range 0,06 … 2,5 m/s 0,2 … 20 m/s 0,05 … 20 m/s 0,06 … 35 m/s
Medium temperature -20 ... +85 °C 0 … +60 °C 0 … +60 °C -20 … +85 °C
Moistness area 0 ... 95 % rF 0 ... 95 % rF 0 ... 95 % rF 0 ... 95 % rF
Specials

SS 20.515 for disinfection with
H2O2 (VHP)
 
SS 20.516 for disinfection with alcohol (with coating)

Bi-directional flow sensor
Switching outputs
Measurement of turbulence degree
Self monitoring function
Detection of contamination ATEX version for Ex-secured areas
Disinfection with H2O2 and alcohols
Bi-directional flow sensor
Switching outputs
Measurement of turbulence degree
Self monitoring function Detection of contamination
Disinfection with H2O2 and alcohols
Protection against corrosion e.g.:
- hydrochloric acid
- caustic soda
- acetone
High precision adjustment
Mounting Sealing (stainless steel)
- Counternut
- Screw adapter
- Shanknut
- Flange bushing
Easy one-hole-mounting Screwed bush
M25 (stainless steel)
Quick mounting system
- Counternut
- Screw adapter
- Shank nut
- Flange bushing
Mounting lengths from 100 to 1.000 mm available
Output signals 0 ... 10 V
0 ... 20 mA
4 ... 20 mA
0 ... 2 V
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
0 ... 2 V
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
Auto UI
4 … 20 mA ↔
0 … 10 V

Application examples:

Cleanroom supervision – monitoring

  • Detection of flow velocity, supervision of filter leakage, control of flow velocity
  • Detection of turbulence degree for estimation of laminarity of cleanroom flow
  • Supervision of flow direction (in case of decrease of pressure or reduction of flow velocity beyond production times

Energy saving and efficiency through

Higher measurement accuracy for efficient reduction of the flow velocity beyond production times (higher accuracy compared to stationed pressure measurement)

Plant monitoring

  • Supervision of plant integrated filter units
  • Control of exhaustion processes with corrosive media
  • Determination of turbulence degrees within one plant

Pharmaceutical Industry

  • Integration in cleanroom-monitoring (Annex1 GMP-guidelines)
  • Charge release in case of decrease of pressure through documentation of flow direction

Semi-conductor Industry

  • Flow monitoring if corrosive process media is present
  • Filter monitoring in clean machines
Keywords:
Flow Sensors for Cleanroom
Related Information
Recommended information
INTL-SENSOR CopyRight
© Copyright By WWW.INTL-SENSOR.COM All Right
tel:86 010-67152280/67114885/67124125
E-mail:pcb@intl-sensor.com
京ICP备07000717号
京公网安备110101000113号