Cleanroom

 

Cleanroom
 
 
 
For the Cleanroom software engineering methodology, see Cleanroom Software Engineering. For the meaning of Cleanroom engineering as a method to avoid copyright infringement, see Clean room design.
A cleanroom is an environment, typically used in manufacturing or scientific research, that has a low level of environmental pollutants such as dust, airborne microbes, aerosol particles and chemical vapors. More accurately, a cleanroom has a controlled level of contamination that is specified by the number of particles per cubic meter at a specified particle size. To give perspective, the ambient air outside in a typical urban environment contains 35,000,000 particles per cubic meter, 0.5 μm and larger in diameter, corresponding to an ISO 9 cleanroom.
 
Overview
Cleanrooms can be very large. Entire manufacturing facilities can be contained within a cleanroom with factory floors covering thousands of square meters. They are used extensively in semiconductor manufacturing, biotechnology, the life sciences and other fields that are very sensitive to environmental contamination.
The air entering a cleanroom from outside is filtered to exclude dust, and the air inside is constantly recirculated through high efficiency particulate air (HEPA) and/or ultra low particulate air (ULPA) filters to remove internally generated contaminants.
Staff enter and leave through airlocks (sometimes including an air shower stage), and wear protective clothing such as hats, face masks, gloves, boots and coveralls.
Equipment inside the cleanroom is designed to generate minimal air contamination. Even specialised mops and buckets exist. Cleanroom furniture is also designed to produce a minimum of particles and to be easy to clean.
Common materials such as paper, pencils, and fabrics made from natural fibers are often excluded; however, alternatives are available. Cleanrooms are not sterile (i.e., free of uncontrolled microbes)[1] and more attention is given to airborne particles. Particle levels are usually tested using a particle counter.
Some cleanrooms are kept at a positive pressure so that if there are any leaks, air leaks out of the chamber instead of unfiltered air coming in.
Some cleanroom HVAC systems control the humidity to low levels, such that extra equipment ("ionizers") are necessary to prevent electrostatic discharge (ESD) problems.
Low-level cleanrooms may only require special shoes, ones with completely smooth soles that do not track in dust or dirt. However, shoe bottoms must not create slipping hazards (safety always takes precedence). Entering a cleanroom usually requires wearing a cleanroom suit.
In other cleanrooms, in which the standards of air contamination are less rigorous, the entrance to the cleanroom may not have an air shower. There is an anteroom (known as a "gray room"), in which the special suits must be put on, but then a person can walk in directly to the room (as seen in the photograph on the right).
Some manufacturing facilities do not use fully classified cleanrooms, but use some cleanroom practices together to maintain their cleanliness requirements.[2][3]
Cleanrooms maintain particulate-free air through the use of either HEPA or ULPA filters employing laminar or turbulent air flow principles. Laminar, or unidirectional, air flow systems direct filtered air downward in a constant stream towards filters located on walls near the cleanroom floor. Laminar air flow systems are typically employed across 80 percent of a cleanroom ceiling to maintain constant air processing. Stainless steel or other non-shed materials are used to construct laminar air flow filters and hoods to prevent excess particles entering the air. Turbulent, or non-unidirectional, air flow uses both laminar air flow hoods and non-specific velocity filters to keep air in a cleanroom in constant motion, although not all in the same direction. The rough air seeks to trap particles that may be in the air and drive them towards the floor, where they enter filters and leave the cleanroom environment.[4]
 
Cleanroom classifications
Cleanrooms are classified according to the number and size of particles permitted per volume of air. Large numbers like "class 100" or "class 1000" refer to FED-STD-209E, and denote the number of particles of size 0.5 µm or larger permitted per cubic foot of air. The standard also allows interpolation, so it is possible to describe e.g. "class 2000".
Small numbers refer to ISO 14644-1 standards, which specify the decimal logarithm of the number of particles 0.1 µm or larger permitted per cubic metre of air. So, for example, an ISO class 5 cleanroom has at most 105 = 100,000 particles per m³.
Both FS 209E and ISO 14644-1 assume log-log relationships between particle size and particle concentration. For that reason, there is no such thing as zero particle concentration. The table locations without entries are non-applicable combinations of particle sizes and cleanliness classes, and should not be read as zero.
Because 1 m³ is approximately 35 ft³, the two standards are mostly equivalent when measuring 0.5 µm particles, although the testing standards differ. Ordinary room air is approximately class 1,000,000 or ISO 9.[5]
US FED STD 209E Cleanroom Standards

Class
maximum particles/ft³
ISO
equivalent
≥0.1 µm
≥0.2 µm
≥0.3 µm
≥0.5 µm
≥5 µm
1
35
7
3
1
 
ISO 3
10
350
75
30
10
 
ISO 4
100
 
750
300
100
 
ISO 5
1,000
 
 
 
1,000
7
ISO 6
10,000
 
 
 
10,000
70
ISO 7
100,000
 
 
 
100,000
700
ISO 8

US FED STD 209E was officially cancelled by the General Services Administration of the US Department of Commerce November 29, 2001,[6][7] but is still widely used.
ISO 14644-1 cleanroom standards

Class
maximum particles/m³
FED STD 209E
equivalent
≥0.1 µm
≥0.2 µm
≥0.3 µm
≥0.5 µm
≥1 µm
≥5 µm
ISO 1
10
2
 
 
 
 
 
ISO 2
100
24
10
4
 
 
 
ISO 3
1,000
237
102
35
8
 
Class 1
ISO 4
10,000
2,370
1,020
352
83
 
Class 10
ISO 5
100,000
23,700
10,200
3,520
832
29
Class 100
ISO 6
1,000,000
237,000
102,000
35,200
8,320
293
Class 1000
ISO 7
 
 
 
352,000
83,200
2,930
Class 10,000
ISO 8
 
 
 
3,520,000
832,000
29,300
Class 100,000
ISO 9
 
 
 
35,200,000
8,320,000
293,000
Room air

BS 5295 cleanroom standards

 
maximum particles/m³
Class
≥0.5 µm
≥1 µm
≥5 µm
≥10 µm
≥25 µm
 
Class 1
3,000
 
0
0
0
 
Class 2
300,000
 
2,000
30
 
 
Class 3
 
1,000,000
20,000
4,000
300
 
Class 4
 
 
200,000
40,000
4,000
 

BS 5295 Class 1 also requires that the greatest particle present in any sample does not exceed 5 μm.[8]
 

 